Capacity | | 2KVA | 3KVA | 4KVA | 5/6KVA | 10KVA | 10KVA | 15KVA | 20KVA |
Input | Voltage | 220VAC ? 25% |
Frequency | 10%/60Hz 10% Auto Sensing |
Output | Voltage | 220VAC ? 1% |
Frequency | 50 ? 0.5% / 60 Hz ? 0.5% (free running) |
Dynamic Repsonse | Full load ? 4% |
Wave Form | Sine Wave |
Crest Factor | 3:1 (for rectifier load) |
Efficiency | > 85% |
Rated output PF | 0.8 - 1 LAG |
Distortion THD | Non-linear load THD < 5%; Linear Load THD < 3% |
Overload | < 130% transfer to Bypass and Recover Automatically after 30s |
130% - 150% Transfer to bypass and recover automatically after 20s |
Battery | Type | Valve Controlled Sealed Lead-Acid Battery |
DC Voltage | 96VDC/192VDC | 192VDC |
Qty for Standard backup | 12V/7Ah x 8pcs/16 pcs | 12V/12Ah x 16 pcs |
Charging Current | 2,5A/5A (10A optional) |
Transfer Time | Bypass to inverter | 0ms |
Inverter to Bypass | < 2ms |
Protection | Short Circuit | Shut off Inverter and Bypass Output |
Over Temperature | Transfer to Bypass automatically |
EMI Filter | 10Hz - 100Hz, 40dB / 100K - 100MHz, 70dB |
Battery | Non fuse breaker |
Display | LCD | Input voltage, Output voltage, Current, Frequency, Battery Voltage, Load, UPS Status, Temperature etc |
Alarm | AC Fault | Alarm every 2 seconds, stop after 90 seconds |
Battery Low Voltage | Continuous alarm every second until UPS shuts down, Battery LED Flash every 2 seconds |
UPS Overload | Continuous Alarm |
UPS Fault | Continuous Alarm |
Communication Interface | RS232 |
Environment | Temperature | 0? - 40?C |
Humidity | < 95% (no condensing) |
Noise (at 1 meter) | <58dB |
Weight (net Weight) | 54Kg+18/36Kg | 58Kg+18/36Kg | 52Kg+36Kg | 54+36Kg | 116Kg | 161Kg | 127Kg | 213Kg |
Dimensions WxDxH (mm) for UPS | 230 x 590 x 540 (L) / 270 x 590 x 750 | 480x340x860 | 480x580x860 | 480x520x940 | 480x620x1000 |