Capacity | | 10KVA | 15KVA | 20KVA | 30KVA | 40KVA | 50KVA |
| | | | | | | |
Input | Voltage | 380VAC ± 20% (3ɸ + 4W) |
Frequency | 50Hz ? 10% / 60 Hz ?10% (Auto sensing) |
Output | Voltage | 220VAC ? 1% |
Frequency | 50 Hz ? 0.05% / 60 Hz ?).05% (free running) |
Dynamic Response | Full Load ? 4% |
Wave Form | Sine Wave |
Crest Factor | 3:1 |
Efficiency | >92% |
Rated PF | 0.8 - 1 LAG |
Overload | Load < 125% after 5 minutes - Transfer to bypass and recover automatically |
Load ≥ 125% - 150% after 30 seconds -Transfer to bypass and recover automatically |
Distortion THD | Non Linear Load THD < 5%; Linear Load THD < 3% |
Battery | Type | Valve Controlled Sealed Lead-acid Battery |
DC Voltage | 192-384VDC | 384VDC |
Battery Quantity | 12V x 16/32 pcs | 12V x 32pcs |
Charging Current | 10A | 10A | 15A | 15A | 20A | 20A |
Transfer time | Bypass to inverter | 0ms |
Inverter to Bypass | < 2ms |
Protection | Short Circuit | Shut off Inverter and Bypass Output at the same time |
Over Temperature | > 85?C Transfer to Bypass Output Automatically |
EMI Filter | EN50091 - 2 |
Battery | Circuit Battery |
Alarm | AC Fault | Alarm every 4 seconds |
Battery Low Voltage | Continuously Alarm every second until UPS shut down, Battery LED Flash every 2 seconds |
Ups Overload | Alarm Continuously |
UPS Fault | Alarm Continuously |
Display | LCD | Input Voltage, Output Voltage, Current, Frequency, Battery Voltage, Load, UPS Status, Temperature |
LED | Input / Bypass / Inverter / Battery / Overload / Fault |
Communication Interface | RS232; Dry Contact |
Environment | Temperature | 0?C - 4?C |
Humidity | <95% (no Condensing) |
Noise (at 1 meter) | <58dB |
Weight (net weight) | 180Kg | 223Kg | 239Kg | 309Kg | 355Kg | 550Kg |
Dimensions WxDxH (mm) for UPS | 680x510x1130 | 740 x 560 x 1200 | 1040x560x1410 |