GENERAL DATA |
Input | Input | Three phase five wire |
Input Voltage | 138VAC - 485VAC |
Input Frequency | 40Hz - 70Hz |
Slow Start | 60 seconds |
Input Total Harmonic Distortion | ≤ 3% |
Input Bypass | Input PF | ≥ 0.999 |
Input Voltage | 380VAC ? 10% |
Input Frequency | 50Hz / 60Hz 0.1Hz |
Battery Voltage | Rated DC Voltage | 380V / 400V / 415V |
Charging Voltage Stability | ? 1% |
DC Output | UPS PF | 0.8 |
Output Voltage | 380V / 400V / 415V |
Output Frequency | 50hHz - 60Kz ? 0.1Hz |
Output Voltage Stability | 380 / 220 VAC ? 1% |
Time for Output Voltage | 20ms (load from 0 - 100%) |
Overload | 110% 60 Minutes |
125% 10 Minutes |
150% 60 Seconds |
1000% 1 Second |
Transfer Time | 0ms |
Crest Factor | ≥ 3:1 |
Distortion THD | ≤3% |
Efficiency | ≥ 96% |
Environment | Temperature | -5?C - 40?C |
Elevation Allowed | ≤1500 meters |
Humidity | ≤95% (no condensing) |
IP Class | IP30 |
Cooling | Air |
Safety Standard | EN60950 |
Electromagnetic Compatibility Characteristics | EN50091-2CLASSB |
Noise | ≤50dB |
Integrated Power Distribution System | Circuit Breaker | Optional |
DC Isolation switch Fuse | Optional |
Lightning Protection | Optional |
PDU Units | Optional |
Others | Dimension for UPS (mm) | 600 x 850 x 2000 | 1200 x 850 x 2000 |
Communication | RS232, RS422, RS485, TCP/IP |
SNMP | Standard |
Structure | Module Parallel, Can Replace Online |
Display | LCD/LED |
Emergency Switch | Optional |
Module Model | HM33 300KVA | HM33 400KVA | HM33 500KVA | HM33 600KVA |
Module Capacity | 40KW, 50KW, 60KW |
DC Input | ? 192VDC |
Input & Output | 3 / 3 |
Dimension for Module | 19" (W) x 3U (H) x 520mm (D) |
Weight | 17Kg | 20Kg |
Input PF | 0.999 |